POWERLINE

     ENGINEERING SERVICES

     
   
     
 

 

Difference between Online, Line interactive and offline UPS.

what is 3,5,9?

"Following a power failure, it can take up to 48 hours to re-configure a multi-terminal or network system" Source: PriceWaterhouse

 

 

 

 

 

 

 

 

 

Our Mission:

"Provide top quality equipments, design an effective engineering power system  to support and facilitate your businesses in a fast growing Information Technology market environment"


Company Profile:

"We are prominent in the marketing and distribution and maintenance of  POWERWARE UPS (Uninterrupted Power Supply) , TELECOMS, POWER SOLUTIONS,  NETWORKING SOLUTIONS, COMPUTERS.

Powerware 9340
Technology: Series 9

Rating: 80-130 kVA
BackupTimes: 5-45 mins typical
Voltage: 380/400/415 V

Typical applications
Information Technology:
- Data Centers
- Server Farms
- Communications
- Broadcasting 
 
Electrical Engineering:

- Industrial Controls
- Process equipment
- Manufacturing Machinery
- Off-shore, military, special projects etc.

Product Highlights
- Harmonic Control with sine-wave input current
- Advanced Battery Management for increased battery life
- DC Expert ensures battery health with online testing
- HotSync for parallel redundancy (Sept '01)
- High system availability with build-in redundant design
- Predictive maintenance features for inherent reliability
- Excellent technical performance
- Easy installation and service
- Software Suite included as standard

Technical Specifications

Input: Power range 80, 100 and 130 kVA at pf 0.8
  Rated voltage 380/400/415 VAC
  Voltage range 342 -456 V
  Frequency 50/60 Hz
  Power Factor > 0.99
  Harmonics 3%THDi
  Efficiency 91% at rated load, 97% with Efficiency Optimizer
  Audible noise 67 dB(A) according to ISO7779
Output: Voltage 380/400/415 VAC +-1%
Control
features:
User interface Graphical Display with LEDS: UPS on, Line on, Battery operation, Bypassed, Overload, Over temperature, Service required, Alarm, Load bar and Audible alarm
  Remote interface 1 pc RS232 port
Two programmable status relays
Four programmable signal inputs
EPO port


 

 Copyright  2003 POWERLINE ENGINEERING SERVICES. All Rights Reserved.